We have probably the most state-of-the-art output equipment, experienced and qualified engineers and workers, recognized good quality manage systems plus a friendly skilled income workforce pre/after-sales support for Changeover Switch Three Phase, Power Correction Capacitor, Inside A Circuit Breaker, We are always looking forward to forming successful business relationships with new clients around the world.
Hot-selling Automotive Circuit Breaker - ZW6-12/630-16(20) Series outdoor high voltage vacuum circuit breaker – Aiso Detail:

General Description

ZW6-12/630-16(20) Series outdoor high voltage vacuum circuit breaker is used for rated voltage 12KV and below, three phases, AC50Hz, power system, to switch on/off loading current, over-current, and short circuit in rural or urban power network, and for similar application, also for sectionalizer of urban 12KV network.

Main Technical Parameters

Technical parameters of breaker as sheet 1

Item

Description

Unit

Data

1

Ratedvoltage

KV

12

2

Ratedinsulationlevel

1minwithstandvoltage

Dry

42

Wet

34

Lightningimpulsewithstandvoltage(peak)

75

3

Ratedcurrent

A

630

4

Ratedfrequency

Hz

50

5

Ratedshortcircuitbreakingcurrent

KA

12.51620

6

Ratedshortcircuitmakingcurrent(peak)

31.54050

7

Ratedpeakwithstandcurrent

31.54050

8

Ratedshorttimewithstandcurrent

12.51620

9

Operatingsequence

 

OC-0.3s-CO-180S-CO

10

Nosofbreakingratedshortcircuitbreakingcurrent

Times

30

11

Mechanicallife

10,000

12

RatedoperatingvoltageCTspringoperatingmechanismprovided

 

DC24,48V,AVDC110V,220V

13

Permissibleabradedthicknessofcontact

mm

3

14

Ratedcurrentofover-currentrelease

A

5

15

Weight

kg

130

Note:Please contact the factory to confirm the latest parameters

Breaker assembly and physical parameters as sheet 2

Item

Description

Unit

Data

1

Openingdistanceofcontact

mm

9±1

2

Overtravellingdistanceofcontact

3±1

3

Averageclosingspeed

s

1.0±0,2

4

Averageopeningspeed

0.6±0.2

5

Jumpingtimeofcontactatclosing

ms

≤2

6

Asychronyofthreephaseopening

7

Closingtime

s

≤0.1

8

Openingtime

Highestoperatingvoltage

≤0.06

Lowestoperatingvoltage

≤0.1

9

DCresistanceofeachphasecircuit

μΩ

≤200

10

Centraldistancebetweenphase(inarcextinguishingchamber)

mm

193

Note:Please contact the factory to confirm the latest parameters

Outline & Installation Size

3b4a06a0-9ab0-45e3-9324-dcb90789c827

Note: If user has any special requirement, please negotiate with our factory.


Product detail pictures:

Hot-selling Automotive Circuit Breaker - ZW6-12/630-16(20) Series outdoor high voltage vacuum circuit breaker – Aiso detail pictures


Related Product Guide:

Our rewards are reduce selling prices,dynamic revenue team,specialized QC,sturdy factories,superior quality services for Hot-selling Automotive Circuit Breaker - ZW6-12/630-16(20) Series outdoor high voltage vacuum circuit breaker – Aiso, The product will supply to all over the world, such as: Bolivia, Colombia, Cologne, We have a professional sales team, they have mastered the best technology and manufacturing processes, have years of experience in foreign trade sales, with customers able to communicate seamlessly and accurately understand the real needs of customers, providing customers with personalized service and unique products.