With our leading technology at the same time as our spirit of innovation,mutual cooperation, benefits and growth, we're going to build a prosperous future together with your esteemed firm for Automatic Static Transfer Switch, Power Surge Arrester, Buy Step Up Transformer, Our ultimate goal is to rank as a top brand and to lead as a pioneer in our field. We are sure our successful experience in tool production will win customer's trust, Wish to co-operate and co-create a better future with you!
Hot-selling Automotive Circuit Breaker - ZW6-12/630-16(20) Series outdoor high voltage vacuum circuit breaker – Aiso Detail:

General Description

ZW6-12/630-16(20) Series outdoor high voltage vacuum circuit breaker is used for rated voltage 12KV and below, three phases, AC50Hz, power system, to switch on/off loading current, over-current, and short circuit in rural or urban power network, and for similar application, also for sectionalizer of urban 12KV network.

Main Technical Parameters

Technical parameters of breaker as sheet 1

Item

Description

Unit

Data

1

Ratedvoltage

KV

12

2

Ratedinsulationlevel

1minwithstandvoltage

Dry

42

Wet

34

Lightningimpulsewithstandvoltage(peak)

75

3

Ratedcurrent

A

630

4

Ratedfrequency

Hz

50

5

Ratedshortcircuitbreakingcurrent

KA

12.51620

6

Ratedshortcircuitmakingcurrent(peak)

31.54050

7

Ratedpeakwithstandcurrent

31.54050

8

Ratedshorttimewithstandcurrent

12.51620

9

Operatingsequence

 

OC-0.3s-CO-180S-CO

10

Nosofbreakingratedshortcircuitbreakingcurrent

Times

30

11

Mechanicallife

10,000

12

RatedoperatingvoltageCTspringoperatingmechanismprovided

 

DC24,48V,AVDC110V,220V

13

Permissibleabradedthicknessofcontact

mm

3

14

Ratedcurrentofover-currentrelease

A

5

15

Weight

kg

130

Note:Please contact the factory to confirm the latest parameters

Breaker assembly and physical parameters as sheet 2

Item

Description

Unit

Data

1

Openingdistanceofcontact

mm

9±1

2

Overtravellingdistanceofcontact

3±1

3

Averageclosingspeed

s

1.0±0,2

4

Averageopeningspeed

0.6±0.2

5

Jumpingtimeofcontactatclosing

ms

≤2

6

Asychronyofthreephaseopening

7

Closingtime

s

≤0.1

8

Openingtime

Highestoperatingvoltage

≤0.06

Lowestoperatingvoltage

≤0.1

9

DCresistanceofeachphasecircuit

μΩ

≤200

10

Centraldistancebetweenphase(inarcextinguishingchamber)

mm

193

Note:Please contact the factory to confirm the latest parameters

Outline & Installation Size

3b4a06a0-9ab0-45e3-9324-dcb90789c827

Note: If user has any special requirement, please negotiate with our factory.


Product detail pictures:

Hot-selling Automotive Circuit Breaker - ZW6-12/630-16(20) Series outdoor high voltage vacuum circuit breaker – Aiso detail pictures


Related Product Guide:

We have state-of-the-art equipment. Our products are exported for the USA, the UK and so on, enjoying a fantastic status among the clients for Hot-selling Automotive Circuit Breaker - ZW6-12/630-16(20) Series outdoor high voltage vacuum circuit breaker – Aiso, The product will supply to all over the world, such as: Thailand, Panama, Turin, As a well educated, innovative and energetic staff,we are responsible for all elements of the research, design, manufacturing, sales and distribution. With studying and developing new techniques,we are not only following but also leading the fashion industry. We listen attentively to the feedback from our customers and provide instant communication. You will instantly feel our expertise and attentive service.